Description
The T-4506 Thermostat is a high volume output, dual temperature, dual dial thermostat. The T-4506 provides individual day and night, or two set point temperature control.
Refer to T-4000 Series Pneumatic Room Thermostat Product Bulletin (LIT-7171060P) for important product information.
Figure 1. T-4506 Dual Temperature Thermostat

Features
	- available in Direct Acting (DIR) and Reverse Acting (REV) models
- includes Fahrenheit dial
- direct acting available in vertical or horizontal model
- reverse acting available in horizontal model
- available with optional manual indexing switch that permits you to restore the day temperature of the individual thermostat without affecting the other system thermostats
- Indexing switch can be unlatched manually or will automatically reset with the day cycle
Repair information
If the T-4506 Dual Temperature Thermostat fails to operate within its specifications, replace the unit. For a replacement thermostat, contact the nearest Johnson Controls® representative.
Selection charts
	
		
			| 
				Table 1. T-4506 Dual Temperature Thermostat 1
				
					
					
					
				
				
					
						| Code number | Description |  
						| T-4506-201 | With Indexing Switch, Switchover at 17 psig | Direct Acting, Horizontal Mounting |  
						| T-4506-202 | Direct Acting, Vertical Mounting |  
						| T-4506-209 | Reverse Acting, Horizontal Mounting |  
						| T-4506-203 | Without Indexing Switch, Switchover at 17 psig | Direct Acting, Horizontal Mounting |  
						| T-4506-204 | Direct Acting, Vertical Mounting |  
						| T-4506-217 | Reverse Acting, Horizontal Mounting |  | 
	
	
		
			| 
				Table 2. Commonly Used Accessories for T-4506
				
					
					
					
				
				
					
						| Code number |  | Description |  
						| T-4002-124 | 
 | Room instrument mounting bracket for surface-mounting thermostats and covers; includes drywall clips, spacers, and mounting templates |  
						| T-4002-122 | 
 | Terminal Connector, with two straight fittings for plug-in connection to5/32 in. O.D. polyethylene tubing |  
						| T-4002-123 | 
 | Terminal Connector, with angle fittings for surface mounted thermostats with exposed tubing |  
						| T-4002-5003 | 
 | Restricted adjustment pin (100/kit) restricts adjustment of set point dial |  
						| T-4002-5012 | 
 | Adjusting knob kit provides a means of external setpoint adjustment |  
						| T-4000-2138 | 
 | Beige Plastic Cover,Horizontal or Vertical (no thermometer, no set point windows) |  
						| T-4000-2139 | 
 | Beige Plastic Cover, Horizontal (no thermometer, no set point windows) |  
						| T-4000-3139 | White Plastic Cover, Horizontal (no thermometer, no set point windows) |  
						| T-4000-2140 | 
 | Beige Plastic Cover, Horizontal, thermometer (no set point windows) |  
						| T-4000-3140 | White Plastic Cover, Horizontal, thermometer (no set point windows) |  
						| T-4756-2141 | 
 | Beige Plastic Cover, Horizontal,2 set point windows (no thermometer) |  
						| T-4756-1738 | 
 | Beige Plastic Cover, Horizontal,2 set point windows with thermometer |  
						| T-4000-2144 | 
 | Beige Plastic Cover, Vertical (no thermometer, no set point windows) |  
						| T-4000-3144 | White Plastic Cover, Vertical (no thermometer, no set point windows) |  
						| T-4756-2145 | 
 | Beige Plastic Cover, Vertical,2 set point windows (no thermometer) |  
						| T-4756-1739 | 
 | Beige Plastic Cover, Vertical,2 set point window with thermometer |  | 
	
Note: For additional accessories, refer to T-4000 Series Accessories.
1 Order cover and mounting bracket separately.
Technical specifications
	
		
			| 
				Table 1. T-4506 Dual Temperature Thermostat technical specifications
				
					
					
				
				
					
						| Code number | Description |  
						| Sensitivity | Adjustable from .75 to 4.0 psig/°F (9 to 50 kPa/°C) Factory set at approximately 2.5 psig/°F (32 kPa/°C) |  
						| Flow capacity | 400 SCIM (107 mL/s) |  
						| Air consumption | 20 SCIM (5 mL/s) |  
						| Supply pressure | 13 to 25 psig (91 to 175 kPa) Nominal Day 15 psig (105 kPa) Nominal Night 20 psig (140 kPa) |  
						| Dial range | 55 to 85°F (Two Dials) |  
						| Air connections | Two (Supply and Output) |  