Johnson Controls TEC3000 Series Proportional Fan Coil Thermostats Installation Guide
Applications
The networked TEC3000 Series Thermostats are stand-alone and field-selectable BACnet® MS/TP or N2 networked devices. Wireless networked models of the TEC3000 Series Thermostat are also available. Proportional Fan Coil and Individual Zone Thermostats provide control of the following:
- Local hydronic reheat valves
- Pressure-dependent variable air volume (VAV) equipment with or without local reheat
- Two- or four-pipe fan coils
- Cabinet unit heaters
- Other individual zone equipment using an on/off or floating control input
The networked models feature a field-selectable Building Automation System (BAS) BACnet MS/TP or N2 communication capability that enables remote monitoring and programming for efficient space temperature control. The wireless models (TEC30xx-xx-000) are compatible only with the WNC1800/ZFR182x Pro Series Wireless Field Bus System that enables communication with a building automation system (BAS). The new wireless models (TEC31xx-14-000) are compatible only with WRG1830/ZFR183x Pro Series Wireless Field Bus System. All models include a USB port configuration that reduces installation time to allow simple backup and restore features from a USB drive, which enables rapid cloning of configuration between similar units.
Some models have occupancy sensing capability built into the device. These thermostats maximize up to 30% energy savings in high-energy usage commercial buildings, such as schools and hotels, during occupied times by using additional standby setpoints.
All models feature an intuitive onboard touchscreen UI with backlit display that makes setup and operation quick and easy. For Single-or Two-Stage Economizer Thermostat models, only the single-speed fan configuration is supported. For TEC3x1x and TEC3x2x models, multiple fan configurations are supported for fan coil equipment types, as follows:
- Single-speed
- Multi-speed (two or three discrete speeds)
- Variable-speed/EC motors (0 to 10 VDC control)
Some models support dehumidification on two-pipe fan coil units with reheat, and four-pipe fan coil units with or without reheat. When no heating is required, the thermostat monitors space humidity and activates dehumidification control as necessary. Heat and/or reheat is used as required to maintain the space temperature. For optimal dehumidification performance, use a fan coil unit that has a multi-speed or variable-speed fan (VSF).
Important: The TEC3000 Series Thermostat is intended to provide an input to equipment under normal operating conditions. Where failure or malfunction of the thermostat could lead to personal injury or property damage to the controlled equipment or other property, additional precautions must be designed into the control system. Incorporate and maintain other devices, such as supervisory or alarm systems or safety or limit controls, intended to warn of or protect against failure or malfunction of the thermostat.
Important : Le TEC3000 Series Thermostat est destiné à transmettre des données entrantes à un équipement dans des conditions normales de fonctionnement. Lorsqu'une défaillance ou un dysfonctionnement du thermostat risque de provoquer des blessures ou d'endommager l'équipement contrôlé ou un autre équipement, la conception du système de contrôle doit intégrer des dispositifs de protection supplémentaires.Veiller dans ce cas à intégrer de façon permanente d'autres dispositifs, tels que des systèmes de supervision ou d'alarme, ou des dispositifs de sécurité ou de limitation, ayant une fonction d'avertissement ou de protection en cas de défaillance ou de dysfonctionnement du thermostat.
North American emissions compliance
Installation
Parts included
- One TEC3000 Series thermostat with integral mounting base
- One installation instructions sheet
Location considerations
For networked models, locate the TEC3000 Series thermostat:
- On a partitioning wall, approximately 5 ft (1.5 m) above the floor in a location of average temperature, to allow for vertical air circulation to the TEC
- Away from direct sunlight, radiant heat, outside walls, outside doors, air discharge grills, stairwells, and from behind doors
- Away from steam or water pipes, warm air stacks, unconditioned areas (not heated or cooled), or sources of electrical interference
- In a clear path between the integrated passive infrared (PIR) occupancy sensor, if equipped, and the space it monitors
For wireless models, also locate the thermostat:
- Outside of a recessed area, metal enclosure, or shelving unit
- On the same building level as the other wireless devices on the same personal area network (PAN)
- At least 2 in. (51 mm) away from any metal obstruction
- In the direct line of sight to other wireless devices on the same PAN. Signal transmission is best if the path between the TEC3000 and other wireless devices is direct as possible. Line of sight is desirable but not required. See Table 1 and Table 2 for the recommended and maximum distances.
- Away from metal and large solid obstructions, that includes equipment rooms and elevator shafts and concrete or brick walls, between the TEC3000 and the ZFR182x or ZFR183x Router/Repeater or ZFR Pro Coordinator Radio
- Within range of two or more wireless devices on the same PAN. Redundancy in the layout provides the best reliability in wireless installations
- At least 20 ft (6 m) from a microwave oven
For integrated passive infrared (PIR) models, make sure that the thermostat is located centrally, where occupant movement is frequent. Ensure that the unit is not blocked by a plastic tamper resistant enclosure (such as the GRD10A-608). The plastic enclosure blocks the occupancy sensing capability.
The use of insulating foam pads is necessary for installations where wiring passes through the wall to the thermostat.
For wireless models, the effective transmission range and distance for indoor applications vary because of wireless signal absorption and reflection due to metal obstructions, walls or floors, and furniture that is found in building interiors.
Note: Allow for sufficient clearance to insert a USB drive into the USB port
Important: Only connect memory devices to the USB port. Do not use it for charging external devices.
Table 1. Indoor line-of-sight transmission ranges ZFR182x
| Range type | Transmission distance | |
|---|---|---|
| WNC Coordinator Router, ZFR Pro Router/Repeater | TEC3000 Wireless Thermostat | |
| Recommended | 50 ft (15.2 m) | 50 ft (15.2 m) |
| Line of Sight, Maximum | 250 ft (76.2 m) | 100 ft (30 m) |
Note: For more details about using ZFR Pro Series communication devices, refer to the WNC1800/ZFR182x Pro Series Wireless Field Bus System Technical Bulletin (LIT-12012356).
Table 2. Indoor line-of-sight transmission ranges ZFR183x
| Range type | Transmission distance | |
|---|---|---|
| WRG Coordinator Router, ZFR Pro Router/Repeater | TEC3000 Wireless Thermostat | |
| Recommended | 250 ft (76.2 m) | 250 ft (76.2 m) |
| Line of Sight, Maximum | 1000 ft (308.4 m) | 1000 ft (308.4 m) |
Note:
- Actual range depends on the site and installation conditions. See Technical Documentation for more information.
- For more details about using ZFR Pro Series communication devices, refer to the WRG1800/ZFR183x Pro Series Wireless Field Bus System Technical Bulletin (LIT-12013553).
Important: ZFR182x Pro Series Wireless System compatible TEC30xx-1x-000 models and ZFR183x Pro Series Wireless System compatible TEC31xx-1x-000 models are not compatible with each other and cannot be used under the same PAN ID (network address).
Figure 1. thermostat shown with occupancy sensor, dimensions, in. (mm)
Table 3. thermostat features
| Callout | Description |
|---|---|
| 1 | Security screw |
| 2 | Display |
| 3 | USB port |
Installing the thermostat
Procedure
- Use a 1/16 in. (1.5 mm) Allen wrench or Johnson Controls® T-4000-119 Allen-Head Adjustment Tool (order separately) to remove the security screw if it is installed on the top of the thermostat cover as illustrated in Figure 1.
- Pull the top edge of the cover and open the thermostat as illustrated in Figure 1.
Important: The cover is not secured on the bottom. Do not drop the cover.
Important: If you are installing more than one thermostat, keep track of which cover attaches to which base. The thermostat version and the base version must match to ensure correct operation.
Important: Use correct Electrostatic Discharge (ESD) precautions during installation and servicing to avoid damage to the electronic circuits of the thermostat.
Figure 1. Removing the security screw and the thermostat cover

- Align the thermostat mounting base on the wall with the security screw on the top and use the base as a template to mark the two mounting hole locations. See Figure 2.Note:
- If you need to install the thermostat on an electrical junction box, use 2-1/2 in. x 4 in. (63 mm x 101 mm) square boxes with mud ring covers and avoid smaller 1-1/2 in. x 4 in.(38 mm x 101 mm) square or 3 in. x 2 in. (76 mm x 51 mm) boxes. This procedure ensures that you have enough space for cabling, if needed.
- For surface-mounted applications, use durable mounting hardware, such as wall anchors, that cannot be easily pulled out of the mounting surface.
- Pull approximately 6 in. (152 mm) of wire from the wall and insert the wire through the center hole in the thermostat mounting base. See Figure 2.
- Secure the mounting base to the wall surface using two mounting screws (user supplied) as illustrated in Figure 2.
Note: Do not overtighten the mounting screws.
Figure 2. Mounting hole locations, dimensions, in. (mm) and securing the thermostat mounting base to the wall

Note: When you mount the unit on the wall, you can hang the front cover on the end of the back cover as illustrated in Figure 3.
Figure 3. Hanging the thermostat front cover

Wiring
About this task
When you replace an existing thermostat, remove and label the wires to identify the terminal functions.
WARNING
- Risk of Electric Shock
- Disconnect the power supply before making electrical connections to avoid electric shock.
Avertissement
- Risque de décharge électrique
- Débrancher l'alimentation avant de réaliser tout raccordement électrique afin d'éviter tout risque de décharge électrique.
CAUTION
- Risk of Property Damage
- Do not apply power to the system before checking all wiring connections. Short circuited or improperly connected wires may result in permanent damage to the equipment.
ATTENTION
- Risque de dégâts matériels
- Ne pas mettre le système sous tension avant d'avoir vérifié tous les raccords de câblage. Des fils formant un court-circuit ou connectés de façon incorrecte risquent d'endommager irrémédiablement l'équipement.
Important: Make all wiring connections in accordance with local, national, and regional regulations. Do not exceed the electrical ratings of the TEC3000 Series thermostat.
Important: Use correct ESD precautions during installation and servicing to avoid damage to the electronic circuits of the thermostat.
To wire the thermostat, complete the following steps:
Procedure
- Strip the ends of each wire 1/4 in. (6 mm) and connect them to the appropriate screw terminals as indicated in Table 1.
Note: For more details on wiring the MS/TP Communications Bus, refer to the MS/TP Communications Bus Technical Bulletin (LIT-12011034).
- Attach the communication wires to the terminal block.
Note: If multiple wires are inserted into the terminals, make sure to twist the wires together before you insert them into the terminal connectors.
- Carefully push any excess wire back into the wall.
Note: Seal the hole in the wall with fireproof material to prevent drafts from affecting the ambient temperature readings.
- For networked models, set the bus end-of-line (EOL) termination switch to the desired location.
You can designate the thermostat as the end of the Field Controller (FC) Bus and N2 Bus through the bus EOL termination switch. The default position is OFF. If the thermostat is at the end of a daisy chain of devices on the FC Bus and N2 Bus, set the EOL switch to the ON position. See Figure 1.
Figure 1. EOL switch position (left) and installing the thermostat cover (right)

- Reattach the thermostat cover to the mounting base, bottom side first.
Important: Make sure you reattach the cover that corresponds to its correct base. The CPU board number needs to match the base board number. Otherwise, an operation error occurs after you reattach a cover and base that do not belong together. The example in Figure 2 indicates that a TEC3612-16 CPU board is mounted on the base of a TEC3312-16. See the following table for TEC3000 model names and code numbers.
Figure 2. Error code indicating mismatched boards

Table 1. TEC3000 model names and code numbers Name Code number Name Code number TEC3012-13 30 TEC3313-14 05 TEC3012-14 31 TEC3322-13 08 TEC3012-16 33 TEC3322-14 09 TEC3013-14 35 TEC3322-16 0B TEC3022-13 38 TEC3323-14 0D TEC3022-14 39 TEC3330-13 10 TEC3022-16 3B TEC3330-14 11 TEC3023-14 3D TEC3330-16 13 TEC3030-13 40 TEC3331-14 15 TEC3030-14 41 TEC3612-13 18 TEC3030-16 43 TEC3612-14 19 TEC3031-14 45 TEC3612-16 1B TEC3112-14 49 TEC3613-14 1D TEC3113-14 4D TEC3622-13 20 TEC3122-14 51 TEC3622-14 21 TEC3123-14 55 TEC3622-16 23 TEC3130-14 59 TEC3623-14 25 TEC3131-14 5D TEC3630-13 28 TEC3312-13 00 TEC3630-14 29 TEC3312-14 01 TEC3630-16 2B TEC3312-16 03 TEC3631-14 2D Note: The two-character code number is listed within the error code to indicate that the CPU board and base board do not belong together.
- Use a 1/16 in. (1.5 mm) Allen wrench or Johnson Controls T-4000-119 Allen-Head Adjustment Tool (order separately) to reinstall the security screw on the top of the thermostat cover. See Figure 1 for security screw placement.
- Remove the protective plastic cover sheet from the display.
Important: If the display is dirty, gently wipe it clean with isopropyl alcohol or ethyl alcohol. Do not scrub hard as to avoid damaging the surface. Do not use other cleaners such as water, ketones, and aromatic solvents, since they may damage the polarizer.
Note:- For VAV and two-pipe systems, connect the valve to the heating output.
- Only one transformer is required for each TEC.
- Power to the AUX contact comes from the reheat coil.
See Wiring diagrams for wiring diagrams. See Table 1 for terminal identification.
Terminal identification
| Terminal label | Function | ||
|---|---|---|---|
| TEC3022, TEC3023, TEC312x Proportional FC/VAV | TEC3322, TEC3323, Proportional FC/VAV | TEC3622, TEC3623 Proportional FC/VAV | |
| 24 V | 24 VAC hot from transformer | ||
| FAN H | Fan high | ||
| FAN M | Fan medium | ||
| FAN L | Fan low and fan on | ||
| AUX | Auxiliary binary output | ||
| AUX | Auxiliary power input | ||
| COM1 | 24 VAC common from transformer | ||
| CLG | Cooling command, configurable 0 VDC to 10 VDC range | ||
| NC | No connection | ||
| NC | No connection | ||
| HTG | Heating command, configurable 0 VDC to 10 VDC range | ||
| RSEN | Configurable analog input 1 | ||
| COS | Configurable analog input 2/Changeover binary switch | ||
| COM | Common | ||
| VSF | Variable speed fan command, configurable 0 VDC to 10 VDC range | ||
| BI-2 | Configurable binary input 2 | ||
| BI-1 | Configurable binary input 1 | ||
| NET+ | n/a | Not connected | Field bus+/N2+ |
| NET- | n/a | Not connected | Field bus-/N2- |
| NET COM | n/a | Not connected | Isolated common for field bus |
1 For the networked models, the common terminals, which do not include NET COM, are internally connected and can be used for all inputs and outputs. For the wireless models, the common terminals are connected and can be used for all inputs, outputs, and 24 VAC power.
Wiring diagrams
See Table 1 for terminal identification.
Figure 1. Proportional wiring diagram
Figure 2. Proportional 0 to 10 VDC control (pressure-dependent VAV)
Figure 3. Proportional 0 to 10 VDC control (pressure-dependent VAV with changeover sensor/switch)
Figure 4. Proportional 0 to 10 VDC control (pressure-dependent VAV with changeover sensor/switch and reheat)
Figure 5. Floating control two-pipe heating and cooling hydronic valve control fan coil application
Figure 6. Floating control two-pipe heating and cooling hydronic valve control with changeover fan coil application
Figure 7. Proportional 0 to 10 VDC control (two-pipe and four-pipe fan coil applications)
Figure 8. AUX contact wiring
Figure 9. Binary input wiring
Setup and adjustments
Important: Table 1 provides a full list of TEC3000 menu settings. In the upcoming sections, step-by-step instructions are included on how to access and adjust the more commonly used menus.
Overview
About this task
Figure 1 shows the thermostat home screen in both the light and dark themes. You can customize it to show or hide various elements from the occupant. See Table 1 for a listing of the touchscreen icons and Table 1 to identify the home screen settings under the Display Settings. When screen customization is used in conjunction with a passcode, the building owner can control which options the occupant can access and adjust.
Important: If lockout levels are used, some icons are hidden. Table 1 provides details of these levels.
Figure 1. thermostat home screen (shown with light and dark themes)
To switch between the modern, classic, light, and dark themes, complete the following steps:
Procedure
- Press the Menu icon.
- Press Settings.
- Press Display Settings.
- Press Change Color Theme.
- Select one of the four options available.
Results
Multiple pages are available on the display. The page that you currently view is emphasized with a filled dot. The other available page displays as an empty dot.
In the modern theme, the cooling, or blue, and heating, or orange, circles show whether the cooling or heating mode is active.
Figure 2. thermostat home screen in cooling mode (left) and heating mode (right)
Customizing the home screen
About this task
Customizing the Home screen settings include:
- Brightness
- Enable Backlight
- Units
- Time
- Time Zone
- Time Format
- Date
- Date Format
You can also show or hide these items on the Home screen:
- Fan Button
- Temperature
- Humidity
- Off Button
- Hold Button
- Setpoint
- Alarms
- Occupancy Status
- Unit Status
- Date/Time
To customize the Home screen, complete the following steps:
Procedure
- Press the Menu icon.
- Press Display Settings.
- Enable or disable elements of the home screen as appropriate for the building owner and occupants.
- Set the passcode on the thermostat to prevent the occupants from changing settings that they should not have access to change.
Touchscreen icons
The following table describes the touchscreen icons on the home screen. Press and release a touchscreen icon to activate the TEC. Additional touchscreen icons appear based on the menu, and those icons are also described in the table.
| Icon | Icon name | Description |
|---|---|---|
| Menu | Displays the configuration screens where various settings may be adjusted. | |
| Alarm | Indicates that the thermostat has triggered an alarm. | |
|
|
Unit Power |
Powers the thermostat on or off.Note:
|
|
|
Humidity |
Indicates the humidity reading. |
|
|
Degree | Indicates that the unit is set to degrees. |
|
|
Network Communication (for Networked Models) No Signal |
Indicates that the thermostat detected a supervisory controller and both are online. Indicates that the thermostat did not detect a supervisory controller. |
|
|
Radio Signal (for Wireless Models) | Indicates the strength of the radio signal. |
|
|
Arrow Up Arrow Down |
Increases or decreases the cooling value on the home screen. |
|
|
Arrow Up Arrow Down |
Increases or decreases the heating value on the home screen. |
| Cooling Hold | Indicates that cooling hold mode is enabled. To disable Hold mode, press the button. | |
| Heating Hold | Indicates that heating hold mode is enabled. To disable Hold mode, press the button. | |
| Cooling Setpoint | Displays the current cooling setpoint. Indicates that Hold mode is disabled. To enable Hold mode, press the button. | |
| Heating Setpoint | Displays the current heating setpoint. Indicates that Hold mode is disabled. To enable Hold mode, press the button. | |
| Setpoint Temperature | Displays the current setpoint temperature. Indicates that the Show Hold button is set to No. | |
| Heating Mode | Indicates that heating mode is selected. | |
| Cooling Mode | Indicates that cooling mode is selected. | |
| Auto Mode | Indicates that Auto mode is selected. | |
|
|
Fan Overrides for Single-speed Fans | Adjusts the fan override between On, Auto, and Quiet for single-speed fans. |
|
|
Fan Overrides for Variable-speed Fans | Adjusts the fan override between On, Auto, and Quiet for variable-speed fans. |
|
|
Fan Overrides for Multi-speed Fans | Adjusts the fan override between Low, Medium, High, Auto, and Quiet for multi-speed fans. |
|
|
Occupancy Status | Adjusts the occupancy between Unoccupied, Occupied, Temporarily Occupied, Standby, Occupancy Override, Unoccupancy Override. |
| Back | Moves the display to the previous screen. | |
| Forward | Moves the display to the next screen. | |
| Home | Returns the display to the main home screen. | |
| Save | Saves the current configuration and parameter settings. | |
| Delete | Deletes the scheduled event. | |
| Clear | Clears the password entry on the keypad screen. | |
| Exclamation point | Indicates that an error has occurred. |
User lockout
You can select from three different levels of access at the local display to manage functionality through the supervisory controller. This lockout is independent of any display or passcode settings. The existing temporary occupancy capability is unaffected by this feature. User lockout hides the icons that are not operable. The following table describes the lockout levels.
| Lockout level | Capability |
|---|---|
| State 0 | Provides full access to Home Screen Display Adjustments and icons (default). |
| State 1 | Hides the Menu icon. |
| State 2 | Only allows the screen to trigger temporary occupancy. Menu, Unit Power, the Up and Down arrows, and Run/Hold are hidden. |
Using the USB port
Use the USB port to quickly and easily load firmware upgrades, back up the current settings, and restore settings to the TEC3000 by using a USB drive. The TEC3000 can recognize eight configuration files or firmware package files. The USB drive format must be FAT or FAT32. The drive cannot be NTFS format or USB 3.0. If you are upgrading firmware or copying configuration files, you need the passcode if one has been set up. Do not remove the USB drive until the firmware upgrade is complete. The TEC3000 may restart and go offline to the network engine after a firmware upgrade. The upgrade takes approximately three minutes.
Configurations are copied, except for the Communication mode. See Choosing the Communication mode (TEC3622 and TEC3623 Models) to configure the networked devices.
Note: TEC3000 Series Thermostats are not compatible with Sandisk USB drives.
Loading the firmware
Procedure
- Ensure that the TEC screen is on.
- Insert the USB drive into the right side of the TEC.
See Figure 1 for the USB port location.
- Press the Menu icon.
- Scroll down the menu and press Update.
- Press Load Firmware.
- Select the correct firmware version. The correct file name has the .pkg extension.
- Press Confirm if you have the correct firmware version.
The firmware is loaded from the USB drive into the TEC3000 operating system. The TEC3000 locates the new firmware only if the new firmware is on the root drive of the USB drive. See Table 1 if the firmware is not loaded correctly.
- Remove the USB drive from the TEC3000 thermostat when the update is complete.
The TEC3000 firmware update is complete when the TEC3000 restarts and returns to the home screen.
Backing up the settings
About this task
Note: When you back up the settings, the network settings are not backed up or restored.
Procedure
- Ensure that the TEC screen is on.
- Insert the USB drive into the right side of the TEC.
See Figure 1 for the USB port location.
- Press the Menu icon.
- Scroll down the menu and press Update.
- Press Backup.
A message appears stating that the file is saved locally and on a USB drive.
- Press Confirm to save locally and on USB.
The setting files are named based on the TEC3000 model name, date, and time stamp. For example, TEC3xx1-00_2018-07-01T1. The files are saved locally and on the USB drive’s root directory. See Table 1 if the settings are not backed up correctly.
- After the settings are saved onto the USB drive, remove the USB drive from the TEC3000.
Scheduled circulation
About this task
You can schedule to run your fan for a minimum duration per hour in order to maintain circulation in a space. If the minimum hourly fan runtime is not exceeded as part of normal HVAC operation, the fan turns on at the end of the hour for the length of time required to fulfill the minimum hourly run time. The fan runtime calculation includes runtime initiated when the Fan Mode is set to On and other overrides. The fan does not turn on if the fan runtime is already longer than the minimum hourly fan runtime. When you enabled the Scheduled Circulation Only When Occupied setting, the fan does not turn on at the end of the hour to fulfill the minimum runtime unless the occupancy state is set to Occupied.
To set the Scheduled circulation, complete the following steps:
Procedure
- Press the Menu icon.
- Press Setup.
- Press General Setup.
- Press Scheduled Circulation and select Enable
- Press Minimum Hourly Fan Runtime and set the time in a range of 5 to 30 minutes.
- Press Scheduled Circulation Only When Occupied and select Disable or Enable as required.
- Press Save and the back arrow to return to the previous screen.
If the fan type is variable speed or multi speed, you can select the speed at which the fan runs to satisfy the minimum hourly runtime.
- In case of variable speed fan, select Variable Speed Fan Circulation Setpoint and set the fan speed for circulation in the range of 0% to 100%.
- In case of multi speed fan, select Multi-Speed Fan Circulation Setpoint and set the fan speed for circulation as Low, Med, or High.
This option is also exposed to the BAS through the points SCH-CIR-EN, SCH-CIR-ONLYOCC, and MIN-HR-FAN. If Scheduled Circulation is disabled, the other two objects show unreliable.
Configurable analog inputs (AIs)
The thermostat supports up to three configurable AIs that can be used to add different features to the system. The configuration menu can be accessed through Setup > Input Setup. All AIs can be configured to support the following options:
- Relative Humidity—Sets up the AI to accept a 0 VDC-10 VDC input when connected to a humidity sensor.
- Remote Zone Temperature—Sets up the AI to accept a resistive input when connected to one of the six supported types of temperature sensors.
- Carbon Dioxide—Sets up the AI to accept a 0 VDC-10 VDC input when connected to a CO2 sensor.
- Damper Feedback—Sets up the AI to accept a 0 VDC-10 VDC input when connected.
- Outdoor Air Temperature—Sets up the AI to accept a resistive input when connected to one of the six supported types of temperature sensors.
- Supply Air Temperature—Sets up the AI to accept a resistive input when connected to one of the six supported types of temperature sensors.
Configuring the AIs
Procedure
- Connect the required sensors to the analog inputs.
- Press the Menu icon.
- Press Setup.
- Press Input Setup.
- Press AI1 Input Selection and select the sensor that is connected to RSEN. If the selected sensor is a Remote Zone Temperature, Outdoor Air Temperature, or Supply Air Temperature sensor, the thermostat restarts.
- Do one of the following after the restart based on the type of sensor you are configuring:
- If the selected sensor is a temperature sensor, do the following:
- a. Press Menu > Setup > Input Setup > AI1 Input Setup and select the temperature sensor that is connected to RSEN.
- b. Press Menu > Setup > Input Setup > AI1 Offset and select the temperature offset as needed for the sensor connected to RSEN. The options are -5°F to 5°F or -2.8°C to 2.8°C.
- If the selected sensor is a Relative Humidity, Carbon Dioxide, or Damper feedback sensor, the Input Setup is automatically set to 0 VDC-10 VDC. Press Menu > Setup > Input Setup > AI1 Offset and select the offset needed for the sensor connected to RSEN. The options are -15% to 15% for Relative Humidity, -200 ppm to 200 ppm for Carbon Dioxide, and -15% to 15% for Damper Feedback.
- If the selected sensor is a temperature sensor, do the following:
- Configure the analog inputs RSEN and COS by following the same steps to set up AI1 Input Selection, AI1 Input Setup, AI1 Offset, AI2 Input Selection, AI2 Setup, and AI2 Offset.
- Complete steps 1 -7 to re-configure the respective AI if you have to change the sensor connected to any of the AIs. When the setup of AI1 Input Selection and AI2 Input Selection changes from resistive type (Remote Zone Temperature and Outdoor Air Temperature) to 0 VDC-10 VDC type (Relative Humidity and Carbon Dioxide) or the other way around, the thermostat restarts.
Networked sensors
The TEC3000 supports sensor values supplied over a network connection. For the TEC3000 to consider the value as reliable, the value must be written to the NET- Override network point at least every 15 minutes. The following table provides a list of point descriptions and the suggested write interval ranges.
| Name | Description | Suggested write interval range |
|---|---|---|
| NET-OAT | Network Override Outdoor Air Temperature | 15 minutes at maximum |
| NET-OAH | Network Override Outdoor Air Humidity | 15 minutes at maximum |
| NET-SAT | Network Override Supply Air Temperature | 30 seconds to 2 minutes |
| NET-ZNH | Network Override Zone Humidity | 5 minutes to 15 minutes at maximum |
| NET-ZNT | Network Override Zone Temperature | 15 seconds to 2 minutes |
| NET-OCC | Network Override Zone Occupancy | 15 minutes at maximum |
Availability of AIs
For TEC3x2x-1x-xxxx models, only the RSEN and COS inputs are available for connection.
Priority for configurable AIs
You cannot set any two AIs to the same function or sensor type for any of the inputs. If two or more AIs are configured as the same, the first configured input is used and the others are ignored. For example, if RSEN and COS are both configured as Relative Humidity, only RSEN is used and COS is ignored.
Priority for overall sensors data sources
The TEC3000 supports various sources of sensor data for use in control or display, including internal sensors, remote sensors that connect using an analog input, or network commanded sensors. The TEC uses the highest priority connected input, which consists of network commands followed by remote sensors and then internal sensors, for control and display. Not all sources are available for all sensors.
Network commands operate on a timeout basis. When a network point is written to by a supervisor, the point becomes the highest priority for 15 minutes. If the supervisor writes a new update within 15 minutes, the timer restarts for another 15 minutes.
Available fault diagnostics
- Supply Fan Faults—The TEC3000 supports a configurable Supply Fan Status feedback input that turns on when the Supply Fan Status does not match the Supply Fan Command, and that you can configure to disable heating, cooling, and fan commands. You can adjust the alarm delay with the Fan Alarm delay setting. If the delay is set to 0 or if you do not define the binary input, this feature becomes disabled.
- Supply Fan Runtime—The TEC3000 supports setting runtime limits on the supply fan command. When the supply fan exeeds the runtime limit, an alarm turns on. This feature acts as a maintenance reminder. Setting the runtime limit to 0 disables this feature.
- Supply Air Temperature Diagnostics—The TEC3000 supports diagnostics when you have a Supply Air Temperature installed. The TEC3000 monitors the supply air. If you call for cooling or heating and the temperature does not fall or rise by at least the supply air temperature alarm offset value within the supply air temperature alarm delay, an alarm generates. If the monitoring occurs while cooling, a cooling ineffective alarm generates. If the monitoring occurs while heating, a heating ineffective alarm generates. If you set the supply air temperature offset value set to 0, this alarm disables.
- Zone Temperature Alarm—When enabled, the user can set a low and high temperature alarm; and if the zone temperature rises or falls below those limits, an alarm generates.
- Trends—Built-in trends exist for many of the inputs and outputs for the TEC3000. These trends are viewable at the TEC. The analog graph displays data in 15-minute increments over the previous 24 hours or a table with the last 25 data points. Binary trends display 25 samples taken at every change of state.
Menus and submenus
In the following table, the * indicates that the menus depend on your configuration.
| Level 1 | Level 2 | Level 3 |
|---|---|---|
| Setpoints | Dehumidification | Dehumidification |
| Cooling Valve Minimum Position* | ||
| Cooling Valve Starting Position* | ||
| Heating Valve Starting Position* | ||
| Coil Tempering Time* | ||
| Dehumidification Overcool Limit* | ||
| Chilled Water Supply Temperature Setpoint* | ||
| Temperature | Occupied Cooling | |
| Occupied Heating | ||
| Unoccupied Cooling | ||
| Unoccupied Heating | ||
| Standby Cooling | ||
| Standby Heating | ||
| Occ Setpoint Select | ||
| Heat Cool Setpoint Mode | ||
| Max Heating Setpoint* | ||
| Min Heating Setpoint* | ||
| Max Cooling Setpoint* | ||
| Min Cooling Setpoint* | ||
| Max Setpoint* | ||
| Min Setpoint* | ||
| Scheduling | Schedule Options | Set Schedule |
| Optimal Start Enable | ||
| Temp Occ Duration | ||
| Motion Sensor Timeout | ||
| Manual Occupancy Mode | ||
| Schedule Source | ||
| Display Settings | Passcode Enabled | |
| Passcode* | ||
| Brightness Setting | ||
| Enable Backlight Timeout | ||
| Units | ||
| Time | ||
| Time Zone | ||
| Set Time Format | ||
| Date | ||
| Set Date Format | ||
| Language | ||
| Show Fan Button on Home | ||
| Show Temp on Home | ||
| Show Humidity on Home | ||
| Show Off Button on Home | ||
| Show Hold Button | ||
| Show Setpoint on Home | ||
| Show Alarms on Home | ||
| Show Occ Status | ||
| Show Unit Status | ||
| Show Date/Time | ||
| Setup | General Setup | Control Mode |
| Unit Enable | ||
| Fan Mode* | ||
| Max Setpoint Offset | ||
| Fan On Delay* | ||
| Fan Off Delay* | ||
| Frost Protection | ||
| Dehum Enable* | ||
| Unocc Dehum Enable | ||
| Dehumidification Sequence Mode* | ||
| Aux Mode | ||
| Load Shed Rate Limit | ||
| Load Shed Adjust | ||
| Fan Alarm Delay | ||
| Fan Alarm Action* | ||
| Fan Alarm Reset* | ||
| Fan Runtime Limit | ||
| Fan Runtime Reset* | ||
| Supply Air Temperature Alarm Offset | ||
| Supply Air Temperature Alarm Delay* | ||
| Unocc Low Speed Fan | ||
| Scheduled Circulation Enable | ||
| Scheduled Circulation Only when Occupied | ||
| Mininum Hourly Fan Runtime | ||
| Variable Speed Fan Circulation Setpoint* | ||
| Multi-speed Fan Circulation Setpoint* | ||
| Input Setup | BI1 Config | |
| BI2 Config | ||
| Supply Temp Sensor* | ||
| Supply Temp Offset* | ||
| Zone Temp Sensor | ||
| Zone Temp Offset | ||
| Humidity Offset | ||
| Reset Sensors | ||
| For networked models:
Zone Temp Alarm Enabled |
||
| For networked models:
Zone Temp Low Limit |
||
| For networked models:
Zone Temp High Limit |
||
| Setup (continued) | Tuning Setup | Temp Control Setup |
| Reset PID Tuning | ||
| Deadband* | ||
| Auto Economizer Tuning | ||
| Heat Prop Band* | ||
| Heat Integral Time* | ||
| Heat Process Range* | ||
| Heat Saturation Time* | ||
| Heat Time Constant* | ||
| Heat Process Dead Time* | ||
| Heat Period* | ||
| Cool Prop Band* | ||
| Cool Integral Time* | ||
| Cool Process Range* | ||
| Cool Saturation Time* | ||
| Cool Time Constant* | ||
| Cool Process Dead Time* | ||
| Cool Period* | ||
| Equipment Size | ||
| Network Setup | FC Comm Mode | |
| BACnet Instance ID* | ||
| For networked models:
N2 Address* |
||
| BACnet Address* | ||
| For networked models:
MSTP Baud Rate* |
||
| BACnet Encoding Type | ||
| BACnet/MSTP Communication Mode | ||
| For wireless models:
Pan ID |
||
| Equipment Setup | General | Unit Type |
| Valve Open Voltage | ||
| Valve Closed Voltage | ||
| Unoccupied Off Delay | ||
| Supply Fan | Supply Fan Type* | |
| Start Voltage* | ||
| Full Speed Voltage* | ||
| Minimum Command* | ||
| Medium Speed On Cmd* | ||
| High Speed On Cmd* | ||
| Reheat | Reheat Installed | |
| Reheat Min Damper Pos* | ||
| Reheat Fan Required* | ||
| Changeover | Changeover Mode* | |
| Supply Temp Type* | ||
| Changeover Setpoint* | ||
| Supply Temp Sensor* | ||
| Supply Temp Offset* | ||
| Trend | EFF-ZNT | |
| EFF-SETPOINT | ||
| EFF-ZNH | ||
| B1 Status | ||
| B2 Status | ||
| EFF-OAT | ||
| EFF-SAT | ||
| FANSPD-S | ||
| HTG-O | ||
| CLG-O | ||
| System Status | Occupancy Source | |
| Unit Status | ||
| Supply Air Temperature | ||
| Changeover State | ||
| Zone Temp Source | ||
| Control Status | Cooling % Command | |
| Heating % Command | ||
| Reheat % Command | ||
| Cool Stage 1 | ||
| Heat Stage 1 | ||
| Reheat Stage 1 | ||
| Fan % Command | ||
| Fan | ||
| Controller Info (Thermostat Info) | Model Name | |
| Software Version | ||
| Unit Name | ||
| Device Name | ||
| Device Description | ||
| Commissioning | Supply Air Temperature | |
| Heat Command | ||
| Cool Command | ||
| Supply Fan | ||
| Aux | ||
| Update | View Version | |
| Load Firmware | ||
| Restore* | ||
| Backup* | ||
| For wireless models:
Network Status |
Radio Code Version | |
| Radio PAN ID | ||
| Active Channel | ||
| Signal Strength | ||
| Connection Status | ||
| Network State | ||
| IEEE Address | ||
| Short Address |
| Sensor type | Mounting style | Probe length | Product code number |
|---|---|---|---|
| Nickel (1k ohm) | Adjustable1 | 8 in. (203 mm) | TE-6311A-1 |
| Averaging | 8 ft (2.4 m) | TE-6315M-1 | |
| TE-6315V-21 | |||
| 17 ft (5.2 m) | TE-6316M-1 | ||
| TE-6316V-21 | |||
| Duct | 4 in. (102 mm) | TE-631GM-1 | |
| 8 in. (203 mm) | TE-6311M-1 | ||
| TE-6311P-1 | |||
| 18 in. (457 mm) | TE-631JM-1 | ||
| Flange | 4 in. (102 mm) | TE-631GV-2 | |
| 8 in. (203 mm) | TE-6311V-2 | ||
| Flush | n/a | TE-6310F-0 | |
| TE-6310F-1 | |||
| Outside air | 3 in. (76 mm) | TE-6313P-1 | |
| Strap-mount | 3 in. (76 mm) | TE-631S-1 | |
| Wall2 | n/a | TE-6314P-1 | |
| Well | 6 in. (152 mm) | TE-631AM-2 | |
| 8 in. (203 mm) | TE-6312M-1 | ||
| Platinum (1k ohm) | Adjustable | 8 in. (203 mm) | TE-6351-A |
| Duct | 4 in. (102 mm) | TE-635GM-1 | |
| 8 in. (203 mm) | TE-6351M-1 | ||
| TE-6351P-1 | |||
| 18 in. (457 mm) | TE-635JM-1 | ||
| Flange | 4 in. (102 mm) | TE-635GV-2 | |
| 8 in. (203 mm) | TE-6351V-2 | ||
| Flush | n/a | TE-6350F-0 | |
| TE-6350F-1 | |||
| Strap-mount | 3 in. (76 mm) | TE-635S-1 | |
| Outside air | 3 in. (76 mm) | TE-6353P-1 | |
| Wall2 | n/a | TE-6324P-1 | |
| Well | 6 in. (152 mm) | TE-635AM-2 | |
| 8 in. (203 mm) | TE-6352M-1 | ||
| Platinum equivalent | 1k ohm averaging1 | 10 ft (3 m) | TE-6327P-1 |
| 20 ft (6.1 m) | TE-6328P-1 | ||
| 100 ohm averaging1 | 10 ft (3 m) | TE-6337P-1 | |
| 20 ft (6.1 m) | TE-6338P-1 | ||
| Thermistor (2.2k ohm) | Adjustable | 8 in. (203 mm) | TE-6341A-1 |
| Duct | 8 in. (203 mm) | TE-6341P-1 | |
| Flange | 4 in. (102 mm) | TE-634GV-2 | |
| 8 in. (203 mm) | TE-6341V-2 | ||
| Outside air | 3 in. (76 mm) | TE-6343P-1 | |
| Wall2 | n/a | TE-6344P-1 | |
| Well | 8 in. (203 mm) | TE-6342M-1 | |
| 6 in. (152 mm) | TE-634AM-2 | ||
| Thermistor (10k ohm) Type II | Adjustable | 8 in. (203 mm) | TE-6361A-1 |
| Duct | 4 in. (102 mm) | TE-636GM-1 | |
| 8 in. (203 mm) | TE-6361M-1 | ||
| TE-6361P-1 | |||
| 18 in. (457 mm) | TE-636JM-1 | ||
| Flange | 4 in. (102 mm) | TE-636GV-2 | |
| 8 in. (203 mm) | TE-6361V-2 | ||
| Flush | n/a | TE-6360F-0 | |
| TE-6360F-1 | |||
| Outside air | 3 in. (76 mm) | TE-6363P-1 | |
| Strap-mount | 3 in. (76 mm) | TE-636S-1 | |
| Well | 6 in. (152 mm) | TE-636AM-2 | |
| 8 in. (203 mm) | TE-6362M-1 |
1 Two TE-6001-8 Element Holders come with the platinum-equivalent averaging sensors. Order separately to use with a nickel averaging sensor.
2 Order the TE-1800-9600 Mounting Hardware separately to mount the wall unit to a wallbox.
Troubleshooting
| Symptom | Probable causes | Solutions |
|---|---|---|
| The thermostat displays Idle with a Unit Status of Cooling Unavailable due to Changeover despite being above cooling setpoint, or with a status of Heating Unavailable due to Changeover despite being below the setpoint. | The two-pipe fan coil/VAV system does not have a changeover sensor and switch connected, or the sensor/switch has failed. |
|
| The changeover temperature senses a hot supply, but the thermostat requests cooling. |
|
|
| Changeover temperature senses a cold supply, but the thermostat requests heating. |
|
|
| The thermostat displays Idle with a Unit Status of Cooling Unavailable due to Control Mode despite being above cooling setpoint, or with a status of Heating Unavailable due to Control Mode despite being below the setpoint. | The Control Mode is set to Cooling Mode, but the thermostat requests heating. | Change the Control Mode to Auto or Heating. |
| The Control Mode is set to Heating Mode, but the thermostat requests cooling. | Change the Control Mode to Auto or Cooling. | |
| The thermostat provides an error when trying to upgrade firmware. | The firmware on the USB drive is below the minimum required version. Error code 1025. |
Please use firmware version 3.0.2.xxxx (for networked models) or 2.0.2.xxxx (for wireless models) or higher. A reboot is required to clear the Firmware Mismatch fault that occurs. |
| The TEC3000 zone temperature does not change fast enough compared to the measured zone temperature from a verification device, such as a calibrated sensor. | The TEC3000 is configured by default for larger spaces with normal-sized equipment when a proportional device is active. | Select Control Setup > Tuning > Equipment Size > Oversized. |
| The zone space temperature increases or decreases too much when the unit is active in unoccupied mode. | The heating and cooling equipment are too big for the unoccupied space. | Decrease the Unoccupied Off Delay parameter from 10 minutes to a more appropriate time for the equipment configuration. |
| The thermostat provides an error when trying to back up settings. | The USB drive is defective. | Try a different USB drive. |
| The thermostat provides an error when trying to restore settings from a backup. | The USB drive is defective. | Try a different USB drive. |
| The Restore file is corrupt. | Try restoring a different backup file. | |
| The Restore file is from an incompatible model TEC. | Ensure that the backup file being restored was from the same model TEC. | |
| The thermostat is unable to access a USB drive. | The drive is formatted as NTFS or another unsupported format. The TEC supports file allocation table (FAT) (for networked models), FAT16 (for wireless models), and FAT32 (for all models) formats only. | Reformat the USB drive, or try a different USB drive with a supported format. |
| The USB drive is defective. | Try a different USB drive. | |
| The thermostat displays Board Mismatch. | The I/O board that the display board is currently attached to does not match the one that initially shipped with the display board. | Attach the display board to the correct I/O board. |
| A hardware failure causes the two boards to incorrectly identify themselves. | Order replacement units and return the affected devices to Johnson Controls under the RMA program. | |
| The thermostat displays Controller Fault (Thermostat Fault). | An internal fault was detected and the thermostat was unable to recover. | Order replacement units and return the affected devices to Johnson Controls under the RMA program. |
| The Bell icon displays on the TEC home page. | The fault has been detected on the TEC. | See Table 1 for TEC fault causes and resolution. |
| Partial Restore Complete is displayed when trying to restore settings from a backup file. | Not all of the items in the backup file have been restored. This error can occur when a value is out of the minimum or maximum range in the backup file. It may also occur if there are inconsistencies in the reliability of a setting in the backup file and on the TEC device. |
|
| The temperature displayed is lower than the actual room temperature. | Cold air drafts enter the back of the TEC. | Seal any holes behind the TEC to reduce drafts. |
| Air is being forced through the TEC from a nearby vent. | Move the location of the TEC or change the venting to prevent air from being forced through the TEC. | |
| For networked models, the Online icon does not appear for a networked thermostat. | There is incorrect field bus wiring. | Refer to the MS/TP Communications Bus Technical Bulletin (LIT-12011034). |
| For wireless models, Supervisory Status = Offline | The supervisory controller is not communicating with the TEC. The TEC is not mapped to a JCI Supervisory System. The WNC or WRG Gateway is not communicating with the TEC. |
|
| Some icons are hidden. | Lockout levels are used or the icons are hidden due to the display settings. | See Table 1 for lockout levels and access details. |
| The touchscreen is unresponsive. | You tap the display or touch the thermostat within 5 mm of the display when power is applied to the controller. | Reboot the thermostat. Do not interact with the thermostat until the home screen displays. |
| You do not tap the touchscreen, but the display acts as if it is tapped, which causes the display to blink or toggle between screens. | ||
| You need to tap the display at an offset from a touch point to activate the display. |
Note: For common MS/TP troubleshooting information, refer to the MS/TP Communications Bus Technical Bulletin (LIT-12011034).
TEC3000 Series Proportional Fan Coil Thermostats technical specifications
| Specification | Description | |
|---|---|---|
| Power requirements | 19 VAC to 30 VAC, 50/60 Hz, 4 VA at 24 VAC nominal, Class 2 or safety extra-low voltage (SELV) | |
| USB port power rating | 120 mA to 250 mA current draw supported | |
| Analog output rating | 0 VDC to 10 VDC into 2k ohm resistance (minimum) | |
| Fan relay output rating | 19 VAC to 30 VAC, 1.0 A maximum, 15 mA minimum, 3.0 A in-rush | |
| Auxiliary output rating/triac output | 19 VAC to 30 VAC, 1.0 A maximum, 15 mA minimum, 3.0 A in-rush | |
| Binary inputs | Dry contact across terminal COM to terminals BI1, BI2, or COS | |
| Analog inputs | Nickel, platinum, A99B, 2.25k ohm NTC, 10k ohm NTC, 10k ohm NTC Type 3 across terminal COM to terminals R SEN or COS | |
| Temperature sensor type | Local digital sensor | |
| Wire size | 18 AWG (1.0 mm diameter) maximum, 22 AWG (0.6 mm diameter) recommended | |
| MS/TP network guidelines | For wired models: Up to 100 devices maximum for each Metasys Supervisory Engine; 4,000 ft (1,219 m) maximum cable length. Refer to the MS/TP Technical Bulletin for the Metasys, FX, or Verasys® system installed. | |
| For wireless models: Up to 100 devices maximum for each Metasys Supervisory Engine | ||
| Wireless band (for wireless models) | Direct-sequence spread-spectrum 2.4 GHz ISM bands | |
| Transmission power (for wireless models) | TEC30xx-1x-000 compatible with ZFR182x Pro Series | 10 mW maximum |
| TEC31xx-1x-000 compatible with ZFR183x Pro Series | 100 mW maximum | |
| Transmission range (for wireless models) | TEC30xx-1x-000 compatible with ZFR182x Pro Series | 50 ft (15.2 m) recommended indoor
250 ft (76.2 m) line of sight, maximum |
| TEC31xx-1x-000 compatible with ZFR183x Pro Series | 250 ft (76.2 m) recommended indoor
1000 ft (304.8 m) line of sight, maximum |
|
| Temperature range | Backlit display | -40.0°F/-40.0°C to 122.0°F/50.0°C in 0.5° increments |
| Heating control | 40.0°F/4.5°C to 90.0°F/32.0°C | |
| Cooling control | 54.0°F/12.0°C to 100.0°F/38.0°C | |
| Accuracy | Temperature | ±0.9F°/±0.5C° at 70.0°F/21.0°C typical calibrated |
| Humidity | ±5% RH from 20 to 80% RH at 50 to 90°F (10 to 32°C) | |
| Minimum Deadband | 2F°/1C° between heating and cooling | |
| Occupancy sensor motion detection (occupancy sensing models) | Minimum of 94 angular degrees up to a distance of 15 ft (4.6 m); based on a clear line of sight | |
| Ambient conditions | Operating | 32°F to 122°F (0°C to 50°C); 95% RH maximum, noncondensing |
| Storage | -22°F to 122°F (-30°C to 50°C); 95% RH maximum, noncondensing | |
| Compliance | BACnet International | BACnet Testing Laboratories™ (BTL) 135-2001 Listed BACnet Advanced Application Controller (B-AAC) |
| United States | UL Listed, File E27734, CCN XAPX, Under UL60730 | |
| Networked models: FCC Compliant to CFR 47, Part 15, Subpart B, Class B | ||
| Wireless models: Transmission complies with FCC Part 15.247 regulations for low power unlicensed transmitters; transmitter identification FCC ID: OEJ-WRZRADIO (ZFR182x), OEJ-ZFRRADIO (ZFR183x) | ||
| Canada | UL Listed, File E27734, CCN XAPX7, Under E60730 | |
| Networked models: Industry Canada, ICES-003 | ||
| Wireless models: Industry Canada (IC) RSS-210;
Transmitter identification ZFR1810-1: IC ID: 279A-WRZRADIO (ZFR182x), 279A-ZFRRADIO (ZFR183x) |
||
| Europe (for networked models only) | CE Mark – Johnson Controls declares that this product is in compliance with the essential requirements and other relevant provisions of the EMC Directive and the RoHS Directive. | |
| Australia and New Zealand | RCM Mark, Australia/NZ Emissions Compliant | |
| Shipping Weight | Models without occupancy sensor | 0.75 lb (0.34 kg) |
| Models with occupancy sensor | 0.77 lb (0.35 kg) | |
The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond these specifications, consult the local Johnson Controls office. Johnson Controls shall not be liable for damages resulting from misapplication or misuse of its products.
Repair information
If the TEC3000 Series thermostat fails to operate within its specifications, replace the unit. For a replacement thermostat, contact the nearest Johnson Controls® representative.
Product warranty
This product is covered by a limited warranty, details of which can be found at www.johnsoncontrols.com/buildingswarranty.
Software terms
Use of the software that is in (or constitutes) this product, or access to the cloud, or hosted services applicable to this product, if any, is subject to applicable end-user license, open-source software information, and other terms set forth at www.johnsoncontrols.com/techterms. Your use of this product constitutes an agreement to such terms.
Patents
Patents: https://jcipat.com
Single point of contact
| APAC | EU | UK | NA/SA |
|---|---|---|---|
|
JOHNSON CONTROLS C/O CONTROLS PRODUCT MANAGEMENT NO. 32 CHANGJIANG RD NEW DISTRICT WUXI JIANGSU PROVINCE 214028 CHINA |
JOHNSON CONTROLS VOLTAWEG 20 6101 XK ECHT THE NETHERLANDS |
JOHNSON CONTROLS TYCO PARK GRIMSHAW LANE MANCHESTER M40 2WL UNITED KINGDOM |
JOHNSON CONTROLS 5757 N GREEN BAY AVE. GLENDALE, WI 53209 USA |
Readmore and Download Johnson Controls TEC3000 Series Proportional Fan Coil Thermostats Installation Guide
| Title | : Johnson Controls TEC3000 Series Proportional Fan Coil Thermostats Installation Guide |
| Format | |
| Pages | : 63 Pages |
| Language | : English |
| File Size | : 10.2 MB |