Emerson 1F85U-22PR (Programmable) Installation and Operating Instructions
80 SeriesTM Universal Thermostat Battery Powered or Hardwired with Common
Emerson 1F85U-22PR SPECIFICATIONS
Electrical Rating:
Battery Power................................... mV to 30 VAC, NEC Class II, 50/60 Hz
Input-Hardwire................................... 20 to 30 VAC, NEC Class II, 50/60 Hz
Terminal Load................................... 1.5 A per terminal, 2.5A maximum all terminals combined
Setpoint Range................................. 45° to 99° F (7° to 37° C)
Rated Differentials (@ 6°F/ Hr): Fast Med Slow
Heat (Conventional Gas / Oil / Elect)... 0.5°F 0.75°F 1.9°F
Cool (Central Air)............................... 0.9°F 1.2°F 1.7°F
Heat Pump (Heat and Cool) ............... 0.9°F 1.2°F 1.7°F
Heat Pump Aux................................. 0.5°F 0.75°F 1.9°F
Operating Ambient............................. 32°F to +105°F (0° to +41°C)
Display Temperature Range................ 32°F to +99°F (0 to 37°C)
Operating Humidity............................ 90% non-condensing maximum
Shipping Temperature Range............. -20°F to + 150°F (-29° to +65°C)
Thermostat Dimensions..................... 3-3/4” H x 6” W x 1-1/8” D
Emerson 1F85U-22PR THERMOSTAT OVERVIEW
Before you begin using your thermostat, you should be familiar with its features, display and the location/operation of the thermostat buttons and switches.
THERMOSTAT BUTTONS AND SWITCHES |
THE DISPLAY |
1.) Fan Button |
8.) Next (Menu button) is used to navigate within a menu |
2.) Hold a permanent temperature or press again to cancel hold (return to programmed schedule) |
9.) Set the correct time, access the schedule and customize thermostat settings |
3.) System Button |
10.) Back (Fan button) is used to navigate within a menu |
4.) Backlight Button (located on the top of the thermostat) |
11.) Exit (Hold/Run button) returns to the home screen |
5.) Raises Temperature Setting |
12.) Thermostat is protecting the equipment from short cycling (5-minute delay) |
6.) Access Menu Options |
13.) Indicates that the system is running in Cool, Heat or Auxiliary mode. (Heat Pump Only -The auxiliary will run in Heat mode when the heat pump cannot maintain the set temperature.) |
7.) Lowers Temperature Setting |
14.) SEE TROUBLESHOOTING |
|
15.) Battery status indicator |
16.) Replace battery indicator |
|
17.) Day of the week used when programming a schedule |
|
18.) Permanent hold (bypassing the schedule) |
|
19.) Temperature setpoint |
|
20.) Appears when the keypad is locked (to prevent unwanted changes) |
Emerson 1F85U-22PR THERMOSTAT WIRING INSTALLATION
Refer to equipment manufacturer’s instructions for specific system wiring information. After wiring, see INSTALLER MENU for proper thermostat configuration. Wiring table shown are for typical systems and describe the thermostat terminal functions. Wiring will change when dedicated emergency heat is on (See Installer Menu #15).
Terminal Designations |
Terminal Function |
RC |
Power (24V) - Cooling |
RH |
Power (24V) - Heating |
O/B 6 (not shown) - 3 wire zone valve |
Reversing Valve or output for 3 wire zone valves Configurable as “O” or “B” Reversing Valve or 3 wire zone heat (power close) |
Y |
1st Stage Compressor (conventional or heat pump) |
G |
Fan Relay |
W/E |
1st Stage Heat (conventional); 1st Stage Auxiliary Heat (heat pump) Can operate as Emergency Heat only (See Installer Menu #15) |
C |
Common wire for 24V (optional with batteries) |
L |
Heat Pump Malfunction / Diagnostic terminal (input signal requires common) |
Y2 |
2nd Stage compressor (conventional only) |
W2 |
2nd Stage Heat (Conventional) Can operate as 1st Stage Auxiliary Heat (See Installer Menu #15) |
Precautions
- Do not exceed the specification ratings.
- All wiring must conform to local and national electrical codes and ordinances.
- This control is a precision instrument, and should be handled carefully. Rough handling or distorting components could cause the control to malfunction.
Emerson 1F85U-22PR THERMOSTAT INSTALLER MENU
To prevent changes that may affect system performance, this thermostat has an INSTALLER MENU and a USER MENU. The INSTALLER MENU provides access to every option, while the USER MENU provides access to items that will not affect system performance. To access the INSTALLER MENU press the Menu button for 8 seconds. The display will show item 05 in the table below. Use Next and Back to navigate through menu items. Press or to change a menu setting.
Installer Menu # (Hold Menu 8 Seconds) |
Description |
Default Setting (flashing icons) |
Settings (Press UP or DOWN) |
05 |
Outdoor Equipment: selects air conditioner (AC) or heat pump (HP) equipment as well as the number of stage |
AC2 |
AC0 AC1 AC2 HP1 |
10 |
Indoor Equipment: selects whether the equipment is a gas furnace, elec- tric furnace or fan only |
EL2 |
FAN GA1 GA2 (conventional only) EL1 EL2 (conventional only) |
15 |
Dedicated Emergency: W/E only operates in Emergency Aux mode. W2 becomes 1st stage Aux. Heat |
OFF |
On OFF |
20 |
O,B or 3 Wire Zone Valve Selection |
O |
O B 3 |
30 |
Heat Cycle Rate: how often the heat will turn on |
MEd |
SLO – slow MEd – medium FAS – fast |
32 |
Aux Cycle Rate: how often the auxiliary heat will turn on |
MEd |
SLO – slow MEd – medium FAS – fast |
35 |
Cool Cycle Rate: how often the cooling will turn on |
MEd |
SLO – slow MEd – medium FAS – fast |
50 |
Compressor Lockout: protects the compressor from short cycling |
OFF |
On – 5 minute delay OFF – no delay |
65 |
Max Heat Limit: maximum set point for heat mode |
99 |
47 to 99 |
66 |
Minimum Cool Limit: minimum set point for cool mode |
45 |
45 to 97 |
INSTALLER MENU (C0ntinued)
Installer’s Menu # (Hold Menu 8 Seconds) |
Description |
Default Setting (flashing icons) |
Settings (Press UP or DOWN) |
74 |
Schedule Type: set as either 7-Day, 5-1-1 Day or Non-Programmable |
5 |
7 – 7 Day 5 – 5-1-1 Day 0 – Non Programmable |
75 |
Defines periods per day |
4 |
2 -leave, return 4 -wake, leave, return, sleep |
76 |
Early Start: starts heating or cooling early so your programmed temperature is reached by the programmed time |
OFF |
On – start early OFF – start at program period time |
79 |
Fahrenheit or Celsius |
°F |
°F – Fahrenheit °C – Celsius |
81 |
Temperature Display Adjustment: adjust the displayed “Room Temperature” |
0 |
-5 to +5 |
83 |
Continuous Display Light: keep the backlight always on – “C” wire required |
OFF |
On – always on OFF – momentarily |
86 |
Change Air Filter: set up a monthly reminder |
OFF |
1 to 12 – reminder time (months) OFF – no filter reminder |
88 |
Auto Changeover: thermostat automatically switches between heat and cool |
OFF |
On – enable auto OFF – disable auto |
99 |
Keypad Lock: prevent unwanted changes to the thermostat |
OFF |
On – disable buttons OFF – all buttons are active |
Emerson 1F85U-22PR TEST EQUIPMENT Turn on power to the system.
Fan Operation
If your system does not have a G terminal connection, skip to Heating System.
- Press the fan button to select the On position. The blower should begin to operate.
- Press the fan button to select the Auto position. The blower should stop immediately.
Heating System
- Press the System button to select the Heat position. Heat Pumps only - if the auxiliary heating system has a standing pilot, be sure to light it.
- Press UP to adjust thermostat setting to 1° above room temperature. The heating system should begin to operate and the thermostat will indicate Heat On.
- For heat pump with auxiliary- Press UP to adjust thermostat setting to 3° above room temperature. The auxiliary heat should begin to operate and the thermostat will indicate Heat On Aux.
- Press DOWN to adjust thermostat setting 1° below room temperature. The heating system should stop operating and the Heat On icon will disappear.
Auxiliary System ( only for heat pumps with auxiliary)
- Press the System button to select the Aux position.
- Press UP to adjust thermostat setting to 1° above room temperature. The auxiliary heating system should begin to operate and the thermostat will indicate Heat On Aux.
- Press DOWN to adjust thermostat setting 1° below room temperature. The auxiliary heating system should stop operating and the Heat On Aux icon will disappear.
Cooling System
- Press the System button to select the Cool position.
- Press DOWN to adjust thermostat setting 1° below room temperature. The blower should come on immediately on high speed, followed by cold air circulation. The thermostat will indicate Cool On. There can be up to a 5 minute delay. (see INSTALLER MENU, item 50)
- Press UP to adjust thermostat setting to 1° above room temperature. The cooling system should stop operating and the Cool On icon will disappear.
Note: If Starting Soon is shown on the display, the compressor lockout feature is operating. There will be up to a 5 minute delay before the compressor turns on (see INSTALLER MENU, item 50).