Emerson With Rodger 1F89-0211 Thermostat Manual
Emerson With Rodger 1F89-0211 SPECIFICATIONS
Electrical Rating:
Battery Power or Hardwire..............20 to 30 VAC, 50/60 Hz
Terminal Load...............................1.5 A per terminal, 2.5A maximum all terminals combined
Setpoint Range.............................45° to 90°F (7° to 32°C)
Differential (Heat Pump).................Heat 1.2°F; Cool 1.2°F (adjustable)
Operating Ambient........................32° to +105°F (0° to +41°C)
Operating Humidity........................90% non-condensing max.
Shipping Temperature Range.......... -40° to +150°F (-40° to +65°C)
Dimensions Thermostat................. 3-3/4”H x 4-3/4”W x 1-1/2”D
Emerson With Rodger 1F89-0211 WIRING DIAGRAM
With Rodger 1F89-0211 THERMOSTAT QUICK REFERENCE
Before you begin programming your thermostat, you should be familiar with its features and with the display and the location and operation of the thermostat buttons and switches (see fig. 3). Your thermostat consists of two parts: the thermostat cover and the base. To remove the cover, pull it straight out from the base. To replace the cover, line up the cover with the base and press until the cover snaps onto the base.
The Thermostat Buttons and Switches
- Raises temperature setting.
- Lowers temperature setting.
- SYSTEM switch (COOL, OFF, HEAT, EMER).
- FAN switch (ON, AUTO).
- Indicates setpoint temperature. This is blank when system switch is in the OFF position. Setpoint temperature is displayed (flashing) if the thermostat is in lockout mode to prevent the compressor from cycling too quickly.
- “AUX” indicates auxiliary stage is operating.
- “Save” indicates the Cool Savings feature is enabled in the configuration menu. “Save” (flashing) indicates Cool Savings feature is active.
- Flame icon is displayed when the SYSTEM switch is in the HEAT position. Flame icon is displayed flashing when thermostat is calling for heat. Snowflake icon is displayed (non-flashing) when the SYSTEM switch is in the COOL position. Snowflake icon is displayed (flashing) if the thermostat is calling for cool.
- Displays current temperature.
- “Service” indicates a diagnostic fault in the heating/ cooling system. It does not indicate a fault in the thermostat.
- “EMER” is displayed flashing when the system switch is in EMER position.
- “Change Filter” is displayed when the system has run for the programmed filter time period as a reminder to change or clean your air filter.
- “Battery Indicator ” indicates when batteries are low and should be replaced.
With Rodger 1F89-0211 Configuration Menu
Menu Reference Number |
Press Key |
Displayed (Factory Default) |
Press or to select from listed options |
Comments |
1 |
UP and DOWN |
CS (OFF) |
On |
Select Cool Savings Feature On or OFF |
UP and DOWN |
CS (3) |
1, 2, 3, 4, 5, 6 |
If CS selected On, selects Cool Savings value |
|
2 |
UP and DOWN |
CR HE-PU (FA) |
SL |
Select Adjustable Anticipation, cycle rate, Heat Pump, Heat and Cool |
3 |
UP and DOWN |
CR Aux (FA) |
SL |
Select Adjustable Anticipation, cycle rate, Heat Pump Aux Stage |
4 |
UP and DOWN
|
CL (OFF) |
On |
Select Compressor lockout OFF or On |
5 |
UP and DOWN |
L (On) |
OFF |
Select Display Light On or OFF |
6 |
UP and DOWN |
Temp (0 HI) |
4 LO to 4 HI |
Select temperature display adjustment higher or lower |
7 |
UP and DOWN |
oF |
oC |
Select oF / oC Display (temperature units in Fahrenheit or Celsius) |
8 |
UP and DOWN |
FH (On) |
OFF |
Select fast second stage On or OFF |
9 |
UP and DOWN |
Change Filter (OFF) |
On |
Select filter replacement indicator OFF or On |
UP and DOWN |
Change Filter (200 h) |
25 to 1975 |
If Change Filter selected On, selects time inter- val for Change Filter Indicator. (in 25 hour increments) |
|
10 |
UP and DOWN |
|
|
Returns to normal operation |
With Rodger 1F89-0211 TROUBLESHOOTING
Reset Operation
If a voltage spike or static discharge blanks out the display or causes erratic thermostat operation, you may need to reset the thermostat. To reset, the System Switch must be in Cool, HEAT, or EMER. Simultaneously hold the UP and DOWN buttons for approximately 10 seconds until the display goes blank. If the thermostat has power, has been reset and still does not function correctly contact your heating/cooling service person or place of purchase.
Symptom |
Possible Cause |
Corrective Action |
No Heat/No Cool/No Fan (common problems) |
|
Replace fuse or reset breaker. Turn switch to ON. Replace door panel in proper position to engage safety interlock or door switch. |
No Heat |
1. System Switch not set to Heat. 2. Loose connection to thermostat or system 3. Heating System requires service or thermostat requires replacement. |
Set System Switch to Heat and raise setpoint above room temperature. Verify thermostat and system wires are securely attached.
Diagnostic: Set System Switch to Heat and raise the setpoint above room temperature. Within a five minutes the thermostat should make a soft click sound. This sound usually indicates the thermostat is operating properly. If the thermostat does not click, try the reset operation listed above. If the thermostat does not click after being reset contact your heating and cooling service person or place of purchase for a replacement. If the thermostat clicks, con- tact the furnace manufacturer or a service person to verify the heating system is operating correctly. |
No Cool |
1. System Switch not set to Cool. |
Set System Switch to Cool and lower setpoint below room temperature. Verify thermostat and system wires are securely attached. Same procedure as diagnostic for No Heat condition except set the thermostat to Cool and lower the setpoint below the room temperature. There may be up to a five minute delay before the thermostat clicks in Cooling if the compressor lock-out option is selected in the configuration menu (Item 4). |
Heat, Cool or Fan Runs Constantly |
1. Possible short in wiring. |
Check each wire connection to verify they are not shorted or touching together. No bare wire should stick out from under terminal screws. Try resetting the thermostat as described below. If the condition persists, the manufacturer of your system or service person can instruct you on how to test the Heat/Cool system for correct operation. If the system operates correctly, replace the thermostat. |
Furnace Cycles Too Fast or Too Slow (narrow or wide temperature swing) |
1. The location of the thermostat and/or the size of the Heating System may be influencing the cycle rate. |
Item 2 in the Configuration Menu is the adjustment that controls the cycle rate. If an acceptable cycle rate is not achieved using the FA (Fast) or SL (Slow) adjustment con- tact a local service person for additional suggestions. |
Cooling Cycles Too Fast or Too Slow (narrow or wide temperature swing) |
1. The location of the thermostat and/or the size of the Cooling System may be influencing the cycle rate. |
The cycle rate for cooling is fixed and can not be adjusted. Contact a local service person for suggestions. |
Thermostat Setting and Thermometer Disagree |
1. Thermostat thermometer setting requires adjustment. |
The thermometer can be adjusted +/- 4 degrees as listed in item 5 of the Configuration Menu. No other adjustment is possible. |
Blank Display and/or Keypad Not Responding |
1. Voltage Spike or Static Discharge. |
If a voltage spike or static discharge occurs use the Reset Operation listed above. |
Thermostat has HP/SS switch and Configuration Menu has selection for HP or SS |
1. Earlier version of thermostat model. |
If switch is present, it must be in HP position for proper fan operation. If selection appears in Configuration Menu, it must be set for HP. |
Readmore and Download Emerson With Rodger 1F89-0211 Thermostat Manual
Title | : Emerson With Rodger 1F89-0211 Thermostat Manual |
Format | |
Pages | : 16 Pages |
Language | : English |
File Size | : 3 MB |
