SPECIFICATIONS
Input Ratings:
Voltage: 18-30 VAC 50/60 Hz transformer of 40 VA or more.
Current Draw:
Zone Panel: 7.5 VA max.
THM4000R Wireless Adapter: 2 VA max.
All VA specifications at 24 VAC.
Wiring:
18- or 20-gauge solid (not stranded) wire.
Humidity Ratings:
5% to 90% RH non-condensing.
Temperature Ratings:
Shipping: -20° to 150°F (-29° to 66°C)
Operating: -40° to 165°F (-40° to 74°C)
Dimensions:
See below.

HZ322 TrueZONE panel dimensions in in. (mm).
Emissions:
Complies with FCC Class B, part 15 requirements.
APPLICATION
The HZ322 TrueZONE® panel controls:
- Conventional gas, oil, or electric forced-air systems up to 2 stages heat and cool;
- Heat pump systems with single stage compressor and auxiliary heat, and two stage heat pumps with no auxiliary heat; and two stage heat pumps with no auxiliary heat;
- 2 or 3 forced-air zones with wired thermostats, or wireless thermostats using THM4000R wireless adapter.
Table 1. Recommended Thermostats.
|
System |
Non-Programmable |
Programmable |
|
SingleStage |
TH5110D, TH3110D, T87N |
TH8110U, TH6110D, TH4110D |
|
Multi- Stage |
TH5220D |
TH8320U, TH8321U, TH6220D, YTH9421C |
|
Heat-Pump |
TH5220D TH3210D |
TH8320U TH8321U TH6220D TH4210D YTH9421C |
|
Wireless* |
TH5320R |
TH6320R |
Note: All versions of the model numbers listed above will work with the applications they're listed for.
For RedLINK™ wireless devices, a THM4000 is required.
Table 2. Recommended Dampers.
|
Type |
Honeywell Damper |
Round |
Rectangular |
|
Zone |
Spring-open/ power-closed |
ARD (6VA) |
ZD (6 VA) |
|
Power-open/ power-closed |
MARD/ RRD (2 VA) |
For recommended dampers call the Honeywell Zoning Hotline at 1-800-828-8367. |
|
|
Bypass |
Static pressure regulating damper |
SPRD/ MARD (2 VA) |
SPRD |
Table 3. Recommended Commercial Dampers.*
|
Type |
Actuation |
Round |
Rectangular |
|
Zone |
Power-open/ power-closed |
MARD |
D2 or D3 with ML6161A2009* |
|
Bypass |
Power-open/ power-closed |
MARD with SPC |
D3 with ML6161B2024* and SPC |
- Or equivalent damper and actuator.
Table 4. Accessories.
|
Accessory |
Description |
|
40 VA transformer* |
AT140A1042* |
|
75 VA transformer |
AT175A1008 |
|
Discharge Air Temperature Sensor * |
DATS C7735A1000* |
|
SDCR** |
Slave Damper Control Relay |
|
Wireless Adapter*** |
THM4000R1000 |
|
Wireless Outdoor Air Temperature Sensor*** |
C7089R1013 |
|
Portable Comfort Control*** |
REM5000R1001 |
|
RedLINK Internet Gateway*** |
THM6000R1002 |
*Included in HZ322K kit.
** Use an SDCR (Slave Damper Control Relay) to add additional dampers to a zone to surpass the maximum Damper VA rating per Zone.
*** For RedLINK™ wireless devices, a THM4000 is required.
MOUNTING
-
Mount the HZ322 TrueZONE panel near the HVAC equipment; locate it on a wall, stud, roof truss, or cold air return.
NOTE: The HZ322 TrueZONE panel can be mounted in any orientation; level it for appearance only.

-
Separate the zone panel cover from the base, and use the base as a template to drill mounting holes. Attach the base to the wall, stud, roof truss, or duct with appropriate screws (not included).

-
Install thermostats using instructions provided with thermostats. Connect thermostat to zone panel. To connect wire to the panel, strip approximately 1/4 in. of insulation and push wire into terminal. To release wire, press the button on top of the terminal. In retrofit applications, trim end of wire if not straight.

The HZ322 offers many innovations for wire management and organization: wires can be run behind the panel, through wire channels on its sides, and must be attached to a wiring anchor with a cable tie. -
Install dampers using instructions provided with dampers. Connect dampers to zone panel.
NOTE: Multiple dampers can be wired in parallel.

-
Connect DATS as shown. For the placement of DATS in supply duct and troubleshooting assistance with the DATS, see the Discharge Air Temperature Installation Instructions Form Number 69-1521.

-
Connect equipment as shown here and on page 5 and 6

-
When a wireless thermostat, Portable Comfort Control, wire- less outdoor air temperature sensor, or other RedLINK™ wireless device is used, wire the THM4000 Wireless Adapter Module to the ABCD terminals on the zone panel.
-
Connect a dedicated transformer as shown.
ADVANCED CONFIGURATION
Use the Adjust Setting, Next, and Back buttons to configure the zone panel. See the Configuration section on page 7 for instructions on using these buttons.
|
Menu Name |
Menu Title (LCD top line) |
Menu Options (LCD bottom line; defaults in bold) |
Menu option description |
Notes: |
|
Heat Fan |
HEAT FAN CONTROL |
[HVAC] PANEL |
Fan control by HVAC |
In heat mode, fan controlled by HVAC or turned on by panel in call for heat. |
|
HVAC [PANEL] |
Fan control by Panel |
|||
|
Stage 2 Timer |
STAGE 2 TIMER |
[5 MIN] > – < [60 MIN] [5 MIN] > |
5 minutes–60 minutes |
Number of minutes to delay before engaging second stage. |
|
Purge Timer |
PURGE TIME |
[2] 3.5 5 MIN |
2.0 minutes |
Number of minutes panel will purge following call for heat or cool. |
|
2 [3.5] 5 MIN |
3.5 minutes |
|||
|
2 3.5 [5] MIN |
5.0 minutes |
|||
|
Purge Fan |
FAN IN PURGE |
[HVAC] PANEL |
Fan control by HVAC |
Fan controlled by HVAC or panel during purge. |
|
HVAC [PANEL] |
Fan control by Panel |
|||
|
Purge Dampers |
PURGE DAMPERS |
[UNCHANGD] OPEN |
Dampers Unchanged |
Damper position unchanged or all dampers open during purge. |
|
UNCHANGD [OPEN] |
Dampers All Open |
|||
|
Auto Changeover Delay |
CHANGEOVER DELAY |
[15] 20 30 MIN |
15 minutes auto changeover timer |
Number of minutes to delay auto changeover when one zone is calling for heat and another is calling for cooling. |
|
15 [20] 30 MIN |
20 minutes auto changeover timer |
|||
|
15 20 [30] MIN |
30 minutes auto changeover timer |
|||
|
DATS Enabled |
DISCHARGE SENSOR |
[NO] YES |
Disabled |
Enables or disables DATS. If Disabled, the Multistage DATS Inhibit setting is Disabled. |
|
NO [YES] |
Enabled |
|||
|
DATS High Limit |
DAT HIGH LIMIT |
[110 F] > – < [180 F] < [160 F] > |
110 deg F–180 deg F |
High temperature limit. |
|
DATS Low Limit |
DAT LOW LIMIT |
[30 F] > – < [60 F] < [40 F] > |
30 deg F–60 deg F |
Low temperature limit. |
|
OT Temp Enabled* |
OT SENSOR |
[NO] YES |
Disabled |
Enables or disables wireless outdoor temperature sensor. If Disabled, the Multistage OT Temp Lockout setting is Disabled. |
|
NO [YES] |
Enabled |
|||
|
OT Trip Point for Multistage Lockout |
OT LOCKOUT TEMP |
[0 F] > – < [50 F] < [50 F] > |
0 deg F–50 deg F |
Above this temperature 2nd stage heat is locked out. |
|
Multistage DATS Inhibit |
DAT MSTG INHIBIT |
NO [YES] |
Enabled |
Allow panel to downstage multistage equipment when near DATS high or low limit. |
|
[NO] YES |
Disabled |
|||
|
LCD Contrast Adjust |
LCD CONTRAST |
[1] > – < [10] < [5] > |
Contrast value 1–10 |
Sets LCD display contrast for ease of viewing. Lowest contrast is 1, highest contrast is 10. |
|
Save Changes |
SAVE CHANGES? |
[NO] YES |
Disabled |
Saves or rejects the configuration settings. |
|
NO [YES] |
Enabled |