Emerson White Rodgers 1E30N-910 installation instructions
Emerson White Rodgers 1E30N-910 SPECIFICATIONS
ELECTRICAL DATA
Switch Rating.............24 VAC (30 VAC max.)
Heating.......................0.15 to 1.2 Amps
Anticipator Rating:
Heating.......................Adjustable from 0.15 to 1.2 Amps
THERMAL DATA:
Temperature Range....50°F to 90°F (10°C to 32°C)
Operating Humidity Range.......0 – 90% noncondensing
YOUR THERMOSTAT REPLACES
|
System |
Models |
|
Standard Heat Only Systems |
1E30N-910 1E50N-301 |
|
Electric Furnace |
|
|
Heat Pump (No Aux or Emergency Heat) |
|
|
Gas or Oil Heat |
|
|
Millivolt Heat Only Systems |
Emerson White Rodgers 1E30N-910 Troubleshooting
|
Symptom |
Possible Cause |
Corrective Action |
|
No Heat/ No Fan |
1. Blown fuse or tripped circuit breaker. |
Replace fuse or reset breaker. |
|
(common problems) |
2. Furnace power switch to OFF. |
Turn switch to ON. |
|
|
3. Furnace blower compartment door or |
Replace door panel in proper position to engage |
|
|
panel loose or not properly installed. |
safety interlock or door switch. |
|
No Heat |
1. Pilot light not lit. |
Re-light pilot. |
|
|
2. Broken or melted anticipator wire. |
Excessive current or dead short in system. Have a qualifi ed service person check the system |
|
|
3. Loose connection to thermostat |
before replacing thermostat. |
|
|
or system. |
Verify thermostat and system wires are securely attached. |
|
|
4. Thermostat or heating system requires |
Your furnace manufacturer or service person can describe how to test the heating system to |
|
|
replacement or service. |
verify it is operating correctly. If the heating system is capable of operation and the no heat |
|
|
5. System Switch not set to Heat.
|
condition persists, replace the thermostat. Set System Switch to Heat and raise temp above room temp. |
|
Intermittent Heat
|
1. Furnace Lock-Out Condition
|
Many furnaces have safety devices that shut the system down when a lock-out condition occurs. If the heat works intermittently contact the furnace manufacturer or local service person for assistance. |
|
Heat or Fan Runs |
1. Possible short in wiring. |
Check each wire connection to the thermostat to verify it is neatly looped under the terminals. |
|
Constantly.
|
|
No extra wire should stick out from under the terminals. |
|
Furnace Cycles Too Fast |
See Step 5, Adjusting the Anticipator. |
The anticipation setting is the only adjustment that effects the heating cycle rate. If an accept- |
|
or Too Slow Narrow or |
|
able cycle rate is not achieved using the anticipator contact a local service person for addi- |
|
wide temperature swing
|
|
tional suggestions. The location of the thermostat, size of the Heat/Cool System and current draw can infl uence the cycle rate. |
|
Thermostat Setting and |
1. Thermostat thermometer setting |
The thermometer can be adjusted by using a standard slotted screwdriver. Turn the thermom- |
|
Thermostat Thermometer |
requires adjustment. |
eter pointer screw located inside the front cover to change the setting. For calibrating the |
|
Disagree
|
2. Thermostat setting lever requires calibration. |
setting lever contact a local heating and cooling service person. |
|
Adjusting Thermometer |
1. Thermostat thermometer disagrees |
The thermometer on the thermostat is accurately calibrated at our factory but you can adjust it |
|
|
with other room thermometers.
|
by using a standard slotted screwdriver. Turn the thermometer pointer screw located inside the front cover to change the setting. |
Emerson White Rodgers 1E30N-910 MOUNTING AND WIRING
- Remove base from subbase or wallplate: Loosen the screws on the base and remove.
- Mount switching subbase or wallplate: Use the screws provided to mount the subbase or wallplate to wall (see Fig. 1).
- Attach wires to appropriate terminals: Two wire systems (Heat Only). Attach one wire to RH and one to wire W.
- Mount Thermostat Base: Gently push excess wire back into the wall opening and plug hole with a fi re-resistant material, such as fi berglass insulation to prevent drafts from affecting thermostat operation. Mount the thermostat base to the subbase or wallplate using the three captive screws on the thermostat base. (See Fig. 1) Tighten the screws securely. Proceed to Step #5.
Readmore and Download Emerson White Rodgers 1E30N-910 Instruction Manual PDF
| Title | : Emerson White Rodgers 1E30N-910 Manual PDF |
| Format | |
| Pages | : 4 Pages |
| Language | : English |
| File Size | : 2 MB |