Honeywell T4039A,B,D-M,S,V Manual
T4039A,B,D-M,S,V Line Voltage Cooling and Heating-Cooling Thermostats
T4039 Thermostats Control Line Voltage Valves of a fan coil unit in cooling, manual changeover heating- cooling, or automatic changeover heating-cooling systems. One or two valves may be controlled directly by the thermostat. The fan switch (where applicable) controls air circulation.
- 1-, 2-, or 3-speed manual fan control available.
- Positive deadspot separates heating-cooling circuits in automatic models. Remote changeover switch is required to separate circuits in manual changeover heating-cooling models.
- Scale range is approximately 55° F to 95° F [13° to 35° C] in 10° F [6° C] increments from 75° F [24° C] midpoint. Scale is marked COOL-WARM.
- Cooling circuit breaks in FAN-OFF position to reduce condensation problems in the fan coil unit.
- Color-coded leadwires.
- All models can be mounted on standard vertical outlet boxes. Models with manual switching can be mounted on 4 in. square junction boxes or 2- ganged outlet boxes.
- Adjustable range stops limit temperature adjustment or lock at selected setpoint.
- Models available with separate power source for fan and thermostat.
Honeywell T4039A,B,D-M,S,V Table of CONTENTS
Specifications .............................................. 2
Ordering Information ..................................... 2
Installation .................................................. 5
Operation .................................................... 8
Checkout .................................................... 8
Honeywell T4039A,B,D-M,S,V Specifications
Models
System |
Manual Switchinga |
Model |
Cooling Only |
Off-Onb |
T4039A |
Cooling Only |
Hi-Med-Lo Off-Onb |
T4039B |
Heating-Coolingc |
— Off-Ond |
T4039D |
Heating Coolingc |
Off-Hi-Lob — |
T4039E |
Heating-Coolingc |
Hi-Med-Lo Off-Onb |
T4039F |
Automatic Heating-Cooling |
None |
T4039G |
Automatic Heating-Cooling |
— Off-Ond |
T4039H |
Automatic Heating-Cooling |
Off-Hi-Lob |
T4039J |
Automatic Heating-Cooling |
Off-Hi-Lod — |
T4039K |
Automatic Heating-Cooling |
Hi-Med-Lob Off-On |
T4039L |
Autoamtic Heating-Cooling |
Hi-Med-Lo Off-Ond |
T4039M |
Automatic Heating-Cooling |
Hi-Med-Lo Heat-Off-Coold |
T4039S |
Automatic Heating-Cooling |
Hi-Lo Off-Ond |
T4039V |
a See Fig. 4 for arrangements of switches.
b OFF breaks cooling circuit and fan circuit.
c Remote changeover switch required.
d OFF breaks both heating and cooling circuits and fan circuit.
ELECTRICAL RATINGS:
A. Thermostat (valve load).
|
Normal (A) |
Inrush (B) |
120 Vac |
0.32 |
1.00 |
240 Vac |
0.16 |
0.50 |
277 Vac |
0.14 |
0.43 |
B. Fan Switch
|
Full Load (A) |
Locked Rotor (A) |
120 Vac |
5.5 |
33.0 |
240 Vac |
2.75 |
16.5 |
277 Vac |
2.4 |
14.4 |
10A |
Resistive at 125 Vac |
|
5A |
Resistive at 240 Vac |
|
4.2A |
Resistive at 277 Vac |
|
TEMPERATURE SETTING RANGE: Approximately 55° F to 95° F [13° C to 35° C]; marked COOLWARM in 10° F [6° C] increments from 75° F [24° C] midpoint.
DIFFERENTIAL: Approximately 2° F [1° C] at midscale. On automatic heating-cooling models, the differential from make of one contact to make of the opposite contact is 7° F [4° C] maximum with a positive deadspot.